GF83.70-S-2002B

Ending heater mode, function

11.9.98

MODEL 638.094 /194 /294 with CODE (H12) Hot water auxiliary heater

MODEL 638.094 /194 /294 with CODE (HZ5) Hot water auxiliary heater 10 KW with timer

Ending heater mode, function

S83.70-2521-06

1 Jacket

2 Coolant inlet

3 Coolant outlet

4 Heater core

5 Burner housing

A34 Hot water auxiliary heater

A34.1 Main wiring harness connector to auxiliary heater

A34.2 Water pump auxiliary heater connector

A87 Hot water auxiliary heater with heater booster function

A87.1 Main wiring harness connector to auxiliary heater with heater booster function

A87.2 Water pump connector auxiliary heater

A72 Auxiliary heater control module

A72.3 Auxiliary heater connector in electric compartment

A74 Auxiliary heater control module with heater booster function

A74.3 Auxiliary heater connector with heater booster function in electric compartment

B94 Coolant temperature switch

B95 Overheating fuse

B96 Flame monitor

M54 Heater booster fuel metering pump

R18 Glow plug

M44 Combustion air blower

M19 Auxiliary heater fuel metering pump

If no malfunctions are present the heater operation can normally be terminated manually on the auxiliary heater control (A7) or automatically after expiration of the normal heating time.

Regardless of the actuation time the operations differs only in terms of the time of actuation.

Heater start-up can be interrupted by the following malfunctions:

Defective flame monitor

Lack of flame formation

The following can lead to premature interruption of the heating period during heater operation:

Overheating,

Voltage too low or too high

Flame interruption

Defective flame monitor or temperature switch

-----------------------------------------------------------------------------------------

Terminating heater operation manually or automatically

1 The combustion is stable. The fuel metering pump (M19/M54) and the combustion air blower (M44) operate at their lowest capacity.

2 The heating mode is terminated manually or automatically.

3 The fuel metering pump (M19/M54) switches off interrupting combustion. The heater blower (M40) switches off.

4 The shut-off delay for cooling the heater and for purging the combustion chamber starts for approx. 120 s. The combustion air blower (M44) operates at partial load for approx. 30 s and at full load for approx. 90 s.

5 The shut-off delay is completed. The combustion air blower and the heater auxiliary pump (M10/M45) switch off. Heater operation is terminated.

-----------------------------------------------------------------------------------------

Flame formation missing

1 Following completion of the safety time the flame monitor (B96) is checked.

2 The flame monitor (B96) signals "cold".

3 The fuel metering pump (M19/M54) and the heater blower (M40) switch off.

4 The shut-off delay for purging the combustion chamber starts for approx. 60 s. The combustion air blower (M44) operates at partial load during the shut-off delay.

5 The shut-off delay is completed. The start-up operation is repeated. The glow plug (R18) switches on and the new start-up procedure starts with a preglowing time of 32 s, safety time of 85 s and flame monitor (B96) check.

6 The flame monitor (B96) signals "cold" again. The hot water auxiliary heater control module (A72/A74) initiates a malfunction shut-off.

7 The fuel metering pump (M19/M54) and the heater blower (M40) switch off.

-----------------------------------------------------------------------------------------

8 The shut-off delay for cooling the heater and for purging the combustion chamber starts for approx. 130 s. The combustion air blower (M44) operates at partial load for approx. 35 s and at full load for approx. 95 s.

9 The shut-off delay is completed. The combustion air blower and the hot water auxiliary pump (M10/M45) switch off.

After eliminating the cause of the malfunction, switch the heater off and back on to reset.

-----------------------------------------------------------------------------------------

Heater overheats

1 The heater is operating at partial load or full load.

2 The coolant temperature increases to above 105 °C and thereby reaches an impermissibly high temperature value.

3 The hot water auxiliary heater control module (A72/A74) recognizes overheating, interrupts the the fuel metering pump (M19/M54) circuit to protect the heater and actuates a malfunction shut-off with following malfunction lockout.

4 The heater blower (M40) switches off.

5 The shut-off delay for cooling the heater and for purging the combustion chamber starts for approx. 120 s. The combustion air blower (M44) operates at partial load for approx. 30 s and at full load for approx. 90 s.

6 The shut-off delay is completed. The combustion air blower and the heater auxiliary pump (M10/M45) switch off.

7 The malfunction shut-off is completed. Restarting the defective heater is no longer possible.

The malfunction lock-out can be reset after eliminating the malfunction by interrupting the power supply.

-----------------------------------------------------------------------------------------

Voltage too low or too high during heater operation

1 The heater is operating at partial or full load.

2 The hot water auxiliary heater control module (A72/A74) recognizes a malfunction in the power supply.

2.1 The voltage is < 9.7 - 10.3 V for more than 20 s.

The control module starts a malfunction shut-off to protect the battery from discharging.

2.2 The voltage increases to 15.5 V for more than 6 s.

The control module starts a malfunction shut-off to protect the electric and electronic heater components.

3 The fuel metering pump (M19/M54) switches off interrupting the combustion.

4 The heater blower (M40) switches off.

5 The shut-off delay for cooling the heater and for purging the combustion chamber starts for approx. 130 s. The combustion air blower (M44) operates at partial load for approx. 35 s and at full load for approx. 95 s.

6 The shut-off delay is completed. The combustion air blower and the heater auxiliary pump (M10/M45) switch off.

-----------------------------------------------------------------------------------------

Flame interruption or defective flame monitor

1 The heater is operating at partial load or full load.

2 The flame monitor (B96) signals "cold". This message can be caused by insufficient fuel or combustion air feed or by a defective flame monitor.

3 The hot water auxiliary heater control module (A72/A74) starts again for approx. 85 s for new flame formation and continuation of the combustion.

4 The combustion air blower (M44) and the fuel metering pump (M54, diesel version) switch from previously full load to partial load. The fuel metering pump (M19/M54, gasoline version) remains at or is switched to full load.

5 The glow plug (R18) switches on and the flame monitor (B96) monitors the start-up attempt.

5.1 The flame monitor signals within the 85 s start-up attempt: "hot" = new flame formation and thereby continuous combustion.

-----------------------------------------------------------------------------------------

5.2 After expiration of the starting attempt of 85 s the flame monitor signals: "cold" = no flame formation and therefore no continuous combustion.

The hot water auxiliary heater control module (A72/A74) starts a malfunction shut-off.

The glow plug (R18), the fuel metering pump (M19/M54) and the heater blower immediately switch off.

The shut-off delay for cooling the heater and for purging the combustion chamber starts for approx. 130 s. During the shut-off delay the combustion air blower operates at partial load for approx. 35 s and at full load for approx.
95 s.

The shut-off delay is completed. The combustion air blower and the heater auxiliary pump (M10/M45) switch off.

After overheating or flame interruption eliminate the cause of the malfunction and reset the heater by switching off and back on.

-----------------------------------------------------------------------------------------

Defective coolant temperature recognition

The coolant temperature is permanently and internally monitored by the hot water auxiliary heater control module (A72/A74).

1 The heater is operating at partial load or full load.

2 The control module recognizes a malfunction in the coolant temperature recognition when the temperature signal has exceeded the temperature recognition range.

3 The control module actuates a malfunction shut-off to protect the heater.

4 The fuel metering pump (M19/M54) switches off and the combustion is interrupted.

5 The heater blower (M40) switches off.

6 The shut-off delay for cooling the heater and for purging the combustion chamber starts for approx. 130 s. The combustion air blower operates at partial load for approx. 35 s and at full load for approx. 95 s.

7 The shut-off delay is completed. The combustion air blower (M44) and the heater auxiliary pump (M10/M45) switch off.

Eliminate the cause of the malfunction and reset the heater by switching off and back on.

Auxiliary heater, location/purpose/design

GF83.70-S-2100A

Timer, location/purpose/design

GF83.70-S-4022A

Heater auxiliary pump, location/ purpose/design/function

GF83.75-S-2103A