Correct oil level in air conditioning system when replacing AC compressor

Vrsta ar · tema 83.55 · različica 0102 · 2019-12-12

Velja za: Model 374.6, 375, 930, 932, 933, 934, 940, 942, 943, 944, 949, 950, 952, 953, 954, 957, 958, 959, 963, 964, 970, 972, 974, 975, 976

Ni na voljo v jeziku »sl«; prikazano v jeziku Angleščina.

Umestitev

Funkcijska skupina 3 Nadgradnja › 83 Klimatizacija › 83.55 Kompresor hladilnega sredstva — Serija 374 (modeli 6**) · Serija 375 · Serija 930 · Serija 932 · Serija 933 · Serija 934 · Serija 940 · Serija 942 · Serija 943 · Serija 944 · Serija 949 · Serija 950 · Serija 952 · Serija 953 · Serija 954 · Serija 957 · Serija 958 · Serija 959 · Serija 963 · Serija 964 · Serija 970 · Serija 972 · Serija 974 · Serija 975 · Serija 976

EinPAS 39 gretje/zračenje/hlajenje › 39.15 klimatizacija › 39.15.1 osnovne informacije — Serija 374 (modeli 6**) · Serija 375 · Serija 930 · Serija 932 · Serija 933 · Serija 934 · Serija 940 · Serija 942 · Serija 943 · Serija 944 · Serija 949 · Serija 950 · Serija 952 · Serija 953 · Serija 954 · Serija 957 · Serija 958 · Serija 959 · Serija 963 · Serija 964 · Serija 970 · Serija 972 · Serija 974 · Serija 975 · Serija 976

AR83.55-W-5250A

Correct oil level in air conditioning system when replacing AC compressor

03.12.2019

Model

374.6, 375, 930, 932, 933, 934, 940, 942, 943, 944, 949, 950, 952, 953, 954, 957, 958, 959, 963, 964, 970, 972, 974, 975, 976

Danger

Risk of explosion caused by welding or soldering work on closed air conditioning system. Risk of poisoning caused by inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant.

Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been drained.

AS83.00-Z-0001-01A

Topical note

Protect air conditioning circuit and components from moisture when carrying out repair work

AH83.30-N-0005-01A

Notes on handling refrigerant R134a

AH83.30-N-0003-01A

Draining

1

Drain new refrigerant compressor.

To do so, drain compressor oil via the openings for the low pressure and high pressure line. Dispose of drained compressor oil properly and in an environmentally friendly manner.

2

Drain removed refrigerant compressor.

Drain compressor oil via openings for low-pressure and high-pressure line and collect with a suitable measuring cup.
Dispose of drained compressor oil properly and in an environmentally friendly manner.

Measure

3

Measure drained oil filling capacity of removed refrigerant compressor.

Filling

4

Fill new refrigerant compressor.

When doing so, fill in the same quantity of compressor oil that has been measured on the removed refrigerant compressor. Always use new compressor oil.