AR83.30-A-1762B | Evacuate air conditioning system, leak test | 18.12.00 |
MODELS 690.34 /63 /64, 903.66 /67 with code (HH6) Air conditioning, roof equipment
MODELS 904.66 with code (HK1) Regulated air conditioning, roof equipment
A83.30-0006-12
Shown on model 690.34 with air conditioning, roof equipment code HH6
1 Test and filling valve, low-pressure side
2 Test and filling valve, high-pressure side side
A83.30-0022-06
Shown on model 904.66 with regulated air conditioning, roof equipment code HK1
1 Test and filling valve, low-pressure side
2 Test and filling valve, high-pressure side
Connect | |||
Danger! | Risk of explosion from welding or soldering work on sealed air conditioning system. Risk of poisoning. Inhaling overheated refrigerant vapors may be toxic. Risk of injury. Contact with liquid refrigerant may result in injury to the skin and eyes. | Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear eye protection and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been discharged. | |
| Notes on handling refrigerant R134a | All models fitted with air conditioning | |
1 | Provide air conditioning extraction, processing and filling unit | | |
2 | Unscrew protective caps from test and filling valve, low-pressure side (1) and test and filling valve, high-pressure side (2) | ||
3 | Connect extraction and filling unit | See manufacturer's operating instructions. | |
Evacuating | |||
4 | Evacuate entire air conditioning system | See manufacturer's operating instructions. | |
Evacuate circuit of the air conditioning after the maximum vacuum has been reached for at least another 30 min. | |||
| Check | ||
5 | After the evacuation process, read the vacuum value at the vacuum pressure gauge | Note vacuum pressure value | |
6 | Wait for 10 min and read off vacuum value at vacuum pressure gauge again | Compare current vacuum value to the recorded vacuum value. If a vacuum reduction > 150 mbar can be detected: | |
Fill air conditioning system After filling the air conditioning system, check for leaky areas: | |||
Inspect the refrigeration circuit for leaks. Before repairing leaky area empty air conditioning system: | |||
Discharge air conditioning system Check for leaky areas again after the repair work: | |||
Repeat steps 3 to 6. |
Workshop equipment
WE58.40-Z-1002-22A | Air conditioning service station |