1 | Diagnostic socket |
2 | Diagnostic socket |
3 | Air conditioning service unit connection |
4 | Air conditioning service unit connection |
P83.30-3970-11
Danger ! | Risk of explosion caused by welding or soldering work on closed air conditioning system. Risk of poisoning caused by inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant. | Do not perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been drained. | |
| Procedure for a damaged or leaky air conditioning system | ||
| Protect air conditioning circuit and components from moisture when carrying out repair work | ||
| Notes on handling refrigerant R134a | ||
Draining | |||
1 | Open engine hood | ||
2 | Unscrew plugs from diagnostic sockets (1, 2) | ||
3 | Connect air conditioning service unit connection (3) to diagnostic socket (1) and air conditioning service unit connection (4) to diagnostic socket (2) | ||
| 000 588 04 82 00 Air conditioning service unit | ||
All operation steps must be carried out in accordance with the operator's manual of the air conditioning service unit. | |||
4 | Suction off refrigerant | Note down oil filling quantity that was suctioned off. | |
Evacuate | |||
5 | Install new desiccant cartridge | Only if refrigerant circuit has been opened. | |
6 | Clean refrigerant and evacuate air conditioning system with air conditioning service unit | ||
Filling | |||
7 | Replace the oil filling quantity noted down during evacuation of the air conditioning system with new compressor oil and route back to the refrigerant circuit | | |
8 | Fill air conditioning system with air conditioning service unit | Refrigerant | |
9 | Disconnect air conditioning service unit connection (4) from diagnostic socket (2) and air conditioning service unit connection (3) from diagnostic socket (1) | ||
10 | Screw on plugs of diagnostic sockets (1, 2) | ||
| Check | ||
11 | Using air conditioning leak detector, inspect air conditioning for leaks at all points at which the system was opened | ||
12 | Close engine hood |
Documente menționate
- ah8330n000301a Indicaţii pentru manipularea refrigerentului R134a
- ah8330n000401a Comportament dacă instalaţia de climatizare este avariată respectiv neetanşă
- ah8330n000501a Protejarea circuitului şi componentelor instalaţiei de climatizare împotriva umidităţii la lucrările de reparaţie
- ar8330p6525ff
- as8300z000101a Pericol de explozie datorită lucrărilor de lipire sau sudură la instalaţia de climatizare oprită. Pericol de otrăvire prin inhalarea de vapori de refrigerent supraîncălziţi. Pericol de rănire prin contactul pielii şi ochilor cu
- ws8300p0031b