Shown on model 613.455 with air conditioning system Konvekta ACX 641 SAPTCO without roof heater, code HKB |
2 | Shutoff valve, pressure side |
3 | Test and filling valve, pressure side |
4 | Test and filling valve, intake side |
5 | Shutoff valve, intake side |
T83.30-0073-06
Filling | |||
Danger | Risk of explosion caused by welding or soldering work on closed air conditioning system. Risk of poisoning caused by inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant. | Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been drained. | |
Topical note | Protect air conditioning circuit and components from moisture when carrying out repair work | ||
Topical note | Procedure for a damaged or leaky air conditioning system | ||
Notes on handling refrigerant R134a | |||
1 | Open electromagnetic shutoff valve |
| |
Electric opening | |||
2 | Evacuate air conditioning system; perform leak test | ||
3 | Charge air conditioning system with refrigerant | Only fill the specified total filling quantity via the test and filling valve, pressure side (3). | |
Total filling capacity - refrigerant | |||
4 | Unscrew shutoff valve, pressure side (2) and shutoff valve, intake side (5) up to end stop | By unscrewing the shutoff valve, pressure side (2) and the shutoff valve, intake side (5), the test and filling valve, pressure side (3) and test and filling valve, intake side (4) are closed. | |
5 | Tighten cover caps on shutoff valve, pressure side (2) and shutoff valve, intake side (5) | ||
6 | Switch off air conditioning vacuum and recycling unit | ||
7 | Remove pressure and suction line of air conditioning vacuum and recycling unit from test and filling valve, pressure side (3) and test and filling valve, intake side (4) | ||
8 | Close electromagnetic shutoff valve | Only if the electromagnetic shutoff valve has been opened with the aid of a magnet. | |
9 | Remove electric line for energization of electromagnetic shutoff valve | Only if the electromagnetic shutoff valve has been opened by energization. |
Odkazované dokumenty
- ah8330n000301a Pokyny k manipulaci s chladivem R134a
- ah8330n000401a Postup při poškozené, resp. netěsné klimatizaci
- ah8330n000501a Ochrana okruhu a součástí klimatizace při opravárenských pracích před vlhkostí
- ar8330t1762bas
- ar8330t1762bas
- ar8330t5460aa
- ar8330t5470bac
- as8300z000101a Nebezpečí exploze při svářečských nebo pájecích pracích na uzavřené klimatizaci. Nebezpečí otravy při vdechnutí přehřátých výparů chladiva. Nebezpečí poranění při kontaktu očí a kůže s tekutým chladivem