963 589 00 91 00
Filling unit
000 589 54 37 00
Clamp
1 | Attach overflow hose (2) to expansion reservoir (1). |
2 | Remove cap from small opening of filling unit and firmly press overflow hose (2) into the fitting. |
W83.30-1228-11
3 | Slide up insulation on return line (5). |
4 | Attach clamping device (4) to return line (5). |
The return line (5) must be tightly sealed with the clamping device (4). Otherwise filling is not possible. |
5 | Open shut-off tap at filling unit. |
The filling unit must be filled with at least 7 liters of coolant for filling the coolant circuit. |
6 | Switch on coolant pump (A41 m1) with Star Diagnosis and allow it to run until bubble-free coolant is flowing out of the overflow hose (2) into the filling unit. |
If after approx. 3 minutes there is still no bubble-free coolant running through the overflow hose, the return line (5) is not sealed airtight by the clamping device (4). |
7 | Close shut-off tap at filling unit. |
8 | Detach clamping device (4) from return line (5). |
9 | Switch off coolant pump (A41 m1) with Star Diagnosis. |
10 | Wait approx. 1 minute until the return line (5) has filled up. |
The fluid level in the expansion reservoir (1) drops. |
11 | Close off return line (5) with clamping device (4). |
12 | Switch coolant pump (A41 m1) on again with Star Diagnosis. |
13 | Open shut-off tap at filling unit and wait until bubble-free coolant is flowing out of the overflow hose (2) into the filling unit. |
14 | Close shut-off tap at filling unit. |
15 | Detach clamping device (4) from return line (5). |
16 | Allow coolant pump (A41 m1) to run for approximately 2 more minutes. All air is removed from the coolant circuit. |
17 | Check the fluid level in the expansion reservoir (1). The fluid level must be level with the "max." mark. If the fluid level has dropped more than 5 mm below the "Max." mark, operation steps 11 to 16 have to be repeated again. |
18 | Detach clamping device (4) from return line (5) |
19 | Disconnect quick coupling of filling unit from service valve (3) of stationary air conditioner. |
20 | Fit cap onto service valve (3). |
21 | Detach overflow hose (2) from expansion reservoir (1). |
22 | Attach cap to expansion reservoir (1). |
W83.30-1231-11