ใช้กับ: MODELS NMB613.355 /358 /388 /455 /485 /364 /365, 671.015 /020 /021 /030 /042 with CODE (HA4) Konvekta air conditioning with roof heater and timer with CODE (HO4) Front air conditioning MODELS NMB613.355 /358 /388 /455 /485 with CODE (HC1) Webasto air conditioning with roof heater MODELS NMB613.355 /358 /388 /455 /485 with CODE (HC1) Webasto air conditioning with roof heater with CODE (HO4) Front air conditioning MODELS NMB613.355 /358 /388 /455 /485 /364 /365 with CODE (HA4) Konvekta air conditioning

ไม่มีใน “th” แสดงเป็น อังกฤษ

ตำแหน่ง

กลุ่มฟังก์ชัน 3 Body › 83 Climate control › 83.30 Air conditioning — ซีรีส์ 613 (รุ่น 355, 358, 364, 365, 367, 388, 455, 485) · ซีรีส์ 671 (รุ่น 015, 020, 021, 030, 042)

EinPAS 39 Heating/ventilation/cooling › 39.15 Climate control › 39.15.5 Air conditioning assembly — ซีรีส์ 613 (รุ่น 355, 358, 364, 365, 367, 388, 455, 485) · ซีรีส์ 671 (รุ่น 015, 020, 021, 030, 042)

AR83.30-T-1780C

Discharge air conditioning system

25.9.00

MODELS NMB613.355 /358 /388 /455 /485 /364 /365, 671.015 /020 /021 /030 /042
with CODE (HA4) Konvekta air conditioning with roof heater and timer
with CODE (HO4) Front air conditioning

MODELS NMB613.355 /358 /388 /455 /485 with CODE (HC1) Webasto air conditioning with roof heater

MODELS NMB613.355 /358 /388 /455 /485
with CODE (HC1) Webasto air conditioning with roof heater
with CODE (HO4) Front air conditioning

MODELS NMB613.355 /358 /388 /455 /485 /364 /365 with CODE (HA4) Konvekta air conditioning with roof heater and timer

MODELS NMB613.358 /388 with CODE (HKD) Konvekta ACX 640 air conditioning with roof heater

MODELS NMB613.358 /388
with CODE (HKD) Konvekta ACX 640 air conditioning with roof heater
with CODE (HO4) Front air conditioning

MODELS NMB613.367 with CODE (HKG) Konvekta ACX 623 air conditioning with roof heater

Discharge air conditioning system

T83.30-0022-11

Shown on models 613.355/455/485

1 Pressure-side testing and filling valve

2 Suction-side testing and filling valve

Discharge air conditioning system

T83.30-0070-11

Shown on model 613.358/388

1 Pressure-side testing and filling valve

2 Suction-side testing and filling valve

Discharge air conditioning system

T83.55-0026-01

Shown on models 613.358/388 with Webasto Top 2002 Aerosphere air conditioning with roof heater code HKD

1 Pressure-side testing and filling valve

2 Suction-side testing and filling valve

3 Shutoff valve on thrust side

4 Shutoff valve on intake side

5 Refrigerant compressor

Modification notes

7.12.04

Activate electromagnetic shutoff valve, added

Step 1

Commercially available tools used, exchanged

Step 2

Screw in shutoff valves 2 to 5 turns, added

Step 3

Fully unscrew shutoff valves, added

Stage 5

Danger!

Risk of explosion from welding or soldering work on closed air conditioning system. Risk of poisoning from inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant.

Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been discharged.

AS83.00-Z-0001-01A

Notes on handling refrigerant R134a

Air conditioning with refrigerant R134a

AH83.30-N-0003-01A

1

Activate electromagnetic shutoff valve

If available.

Depending on the model and the version, the electromagnetic shutoff valve has to be activated in order to be able to fully evacuate the refrigerant from the system.

Usually, the electromagnetic shutoff valve is located between the fluid reservoir and the expansion valve.

Models 613.355/455/485/358/388/364/365
with Konvekta air conditioning with roof heater and timer code HA4,
models 671.015/020/021/030/042 with Konvekta air conditioning with roof heater and timer code HA4 with front air conditioning code HO4,
models 613.355/455/485/358/388 with Webasto air conditioning with roof heater code HC1

Models 613.358/388 with Konvekta ACX 640 air conditioning with roof heater code HKD,
model 613.367 with Konvekta ACX 623 air conditioning with roof heater code HKG

AR83.30-T-5470BAC

Cable for activation of solenoid

All models

WF58.50-T-8330-01A

2

Connect pressure and suction line of air conditioning vacuum and recycling unit to the pressure-side testing and filling valve (1) and to the suction-side testing and filling valve (2)

Observe the operator's manual of the air conditioning vacuum and recycling unit.

*WE58.40-Z-1002-22A

3

Screw in pressure-side shutoff valve (3) and suction-side shutoff valve (4) approx. 2 to 5 turns

The pressure-side shutoff valve (3) and the suction-side shutoff valve (4) are located below the protective caps.

4

Extract refrigerant via the pressure-side testing and filling valve (1) and the suction-side testing and filling valve (2)

Observe the following:

Slowly open the valves at the pressure gauge of the air conditioning vacuum and recycling unit.

Observe the indication on the display of the air conditioning vacuum and recycling unit.

Extract the refrigerant until no further weight gain of the extracted refrigerant can be detected.

5

Fully unscrew pressure-side shutoff valve (3) and suction-side shutoff valve (4)

6

Switch off air conditioning vacuum and recycling unit, remove suction and pressure line

Workshop equipment

WE58.40-Z-1002-22A

Air conditioning service station