Model | NMB613.455 |
with code HKB (Konvekta ACX 641 SAPTCO air conditioning without roof heater) | |
except code H92 (No roof heater) | |
Model | NMB613.455 |
with code HKE (Konvekta ACX 642 air conditioning with roof heater) | |
except code H92 (No roof heater) | |
Model | NMB613.358/388 |
with code HKD (Konvekta ACX 640 air conditioning with roof heater) | |
except code H92 (No roof heater) |
Shown on model 613.455 with code HKB (Konvekta air conditioning system, 641 SAPTCO without roof heater) |
1 | Electrical shutoff valve |
2 | Manual shutoff valve |
3 | Filling valve |
4 | Clip |
5 | Filter drier |
6 | Refrigerant line |
T83.50-0034-11
| Remove/install | ||
Danger | Risk of death caused by falling from vehicle roof. Risk of injury to other persons caused by falling objects during work in roof area. | ||
Danger | Risk of explosion caused by welding or soldering work on closed air conditioning system. Risk of poisoning caused by inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant. | Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been drained. | |
Topical note | Protect air conditioning circuit and components from moisture when carrying out repair work | ||
Topical note | Procedure for a damaged or leaky air conditioning system | ||
Notes on handling refrigerant R134a | |||
1 | Remove cover over filter dryer (5) |
| |
Model NMB613.455 | |||
Only remove cover above rear window. | |||
2 | Screw in manually operated shut-off valve (2) all the way | The manually operated shut-off valve (2) is located under the protective nuts. | |
3 | Connect air conditioning evacuation and recycling unit to filling valve (3) | Observe operator's manual for air conditioning system evacuation and recycling unit. | |
4 | Empty closed-off circuit of filter dryer (5) through filling valve (3) using air conditioning system evacuation and recycling unit | Installation: Evacuate closed-off circuit of filter dryer (5) through filling valve (3) using air conditioning system evacuation and recycling unit for at least 15 minutes then check for leak tightness. | |
5 | Remove refrigerant line (6) from filter dryer (5) | ||
| Compressor oils (specification 362.0) | ||
Installation: Use new sealing rings. Coat sealing rings with compressor oil before installation. | |||
Refrigerant line to filter drier | |||
6 | Loosen and remove clamp (4) | ||
Warning | Risk of injury caused by damaged assemblies filled with refrigerant | Wear protective clothing, safety gloves and safety glasses. | |
7 | Remove filter dryer (5) | Installation: Check packaging of filter dryer (5) for damage. Dispose of filter dryer (5) if packaging is damaged. | |
8 | Install in the reverse order | ||
9 | Check refrigerant level of air conditioning system | ||
| |||
10 | Perform function test | ||
| Air conditioning system - function check | Model NMB613.455 | |
| Air conditioning system - function check | Model NMB613.455 | |
| Air conditioning system - function check | Model NMB613.358/388 |
参照文書
- ah8330n000301a 冷媒 (R134a) の取扱いについての注意事項
- ah8330n000401a 損傷または漏れがあるエアコンの取扱い
- ah8330n000501a リペア作業時のエアコンの冷媒回路および構成部品の水分付着からの保護
- ap8300t8352bac
- ap8300t8352bad
- ap8300t8352bas
- ap8330t8312bas
- ar8350t500001bas
- ar8350t5015bac
- as6500z000201a 車両ル一フからの落下により生命に関わる危険。ル一フ部作業時に落下物により、他の人を負傷させる危険。
- as8300z000101a 密閉したエアコンに対して溶接作業またはハンダ付け作業を行うことによる爆発の危険。加熱した冷媒のガスを吸い込むことによる中毒の危険。肌や眼に液状の冷媒が触れるこ�
- as8661z000101a 冷媒が充填されたユニットの損傷による負傷の危険
- bb0040p036200a コンプレッサオイル(明細仕様 362.0)