Model | 903.663 |
Minibus Sprinter Group, with rear air conditioning system SC1-9 | |
Model | 903.663 |
Minibus Sprinter Group, with rear air conditioning system SC4-10 | |
Model | 904.663 |
Minibus Sprinter Classic, with rear air conditioning system SC2-10 | |
Model | 904.663 |
Minibus Sprinter Classic, with rear air conditioning system SC3-11 with additional condenser | |
Model | 904.663 |
Minibus Sprinter Eco, with rear air conditioning system SC1-9 | |
Model | 904.663 |
Minibus Sprinter Group, with rear air conditioning system SC1-9 | |
Model | 904.663 |
Minibus Sprinter Group, with rear air conditioning system SC4-10 | |
Model | 904.663 |
Minibus Sprinter low floor, with rear air conditioning system SC2-10 | |
Model | 904.663 |
Minibus Sprinter low floor, with rear air conditioning system SC3-11 with additional condenser | |
Model | 904.663 |
Minibus Sprinter Tourist, with rear air conditioning system SC3-10 | |
Model | 904.663 |
Minibus Sprinter Tourist, with rear air conditioning system SC5-10 | |
Model | 905.613 |
Minibus Sprinter Classic 6 t, with rear air conditioning system SC3-11 with additional condenser | |
Model | 905.613 |
Minibus Sprinter low-floor 6 t, with rear air conditioning system SC3-11 with additional condenser |
M83.50-0035-09
1 | Bitumen insulation tape | 4 | Union nut | 7 | Union nut | ||
2 | Refrigerant line pressure side | 5 | Refrigerant pressure capillary | 8 | Mounting clamp | ||
3 | Expansion valve | 6 | Temperature sensor |
| Remove/install | ||
Danger | Risk of explosion caused by welding or soldering work on closed air conditioning system. Risk of poisoning caused by inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant. | Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been drained. | |
Topical note | Protect air conditioning circuit and components from moisture when carrying out repair work | ||
Topical note | Procedure for a damaged or leaky air conditioning system | ||
Notes on handling refrigerant R134a | |||
1 | Drain air conditioning system | ||
2 | Remove evaporator unit trim | ||
3 | Remove bitumen insulation tape (1) in area of expansion valve (3) | Installation: Wrap area around expansion valve (3), low-pressure switch and the evaporator pipe lines carefully with new bitumen insulation tape (1). | |
Insulation | |||
4 | Unscrew union nuts (4) and remove capillary (5) | ||
| |||
Plug openings. | |||
Installation: Install new sealing rings. Coat sealing rings with compressor oil before installation. | |||
Nut, connection for refrigerant pressure capillary tube | |||
Record plug | |||
5 | Unscrew pressure-side refrigerant line (2) from expansion valve (3) | ||
| |||
Plug openings. | |||
Installation: Replace seal. Coat sealing ring with compressor oil before installation. | |||
Connector for refrigerant lines | |||
Record plug | |||
6 | Remove mounting clamp (8) from temperature sensor (6) | Installation: The temperature sensor (6) must be attached to the upper side of the evaporator pipe. | |
7 | Unscrew union nut (7) and remove expansion valve (3) | ||
| |||
Plug openings. | |||
Installation: Replace seal. Coat sealing ring with compressor oil before installation. | |||
Connector for refrigerant lines | |||
Record plug | |||
8 | Install in the reverse order | Only attach evaporator unit paneling after the air conditioning has been topped up and checked. | |
9 | Replace air conditioning system filter drier | ||
10 | Evacuate air conditioning system, charge it, and then check system to make sure that it functions correctly and does not leak |
129 589 00 91 00
Record plug
Referenced documents
- ah8330n000301a Notes on handling refrigerant R134a
- ah8330n000401a Procedure for a damaged or leaky air conditioning system
- ah8330n000501a Protect air conditioning circuit and components from moisture when carrying out repair work
- ar8330m1760a Drain, evacuate and recharge air conditioning, check for proper operation and check for leaks
- ar8330m1760a
- ar8330m6525a
- ar8330m6525a Remove/install dehydrator
- ar8350m5010a Remove/install evaporator unit paneling
- as8300z000101a Risk of explosion caused by welding or soldering work on closed air conditioning system. Risk of poisoning caused by inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant.
- bb0040p036200a Compressor oils (specification 362.0)