AR83.30-T-1780BAF | Discharge air conditioning system | 8.2.05 |
MODELS NMB613.358 /388 with CODE (HKF) Webasto Top 2002 Aerosphere air conditioning with roof heater
MODELS NMB613.358 /388
with CODE (HKF) Webasto Top 2002 Aerosphere air conditioning with roof heater
with CODE (HO4) Front air conditioning
T83.55-0025-01
3 Shutoff valve on thrust side
4 Shutoff valve on intake side
11 Pressure-side testing and filling valve
12 Suction-side testing and filling valve
Danger! | Risk of explosion from welding or soldering work on closed air conditioning system. Risk of poisoning from inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant. | Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been discharged. | |
| Notes on handling refrigerant R134a | Air conditioning with refrigerant R134a | |
1 | Energize electromagnetic shutoff valve | ||
| Cable for activation of solenoid | ||
2 | Detach protective caps from the pressure-side testing and filling valve (11) and from the suction-side testing and filling valve (12) | ||
3 | Connect pressure and suction line of the air conditioning extraction and recycling unit to the pressure-side testing and filling valve (11) and to the suction-side testing and filling valve (12) | Refer to the operating instructions for the air conditioning extraction and recycling unit. Ensure that the pressure-side shutoff valve (3) and the suction-side shutoff valve (4) are unscrewed completely. | |
| |||
4 | Extract refrigerant using the pressure-side testing and filling valve (11) and the suction-side testing and filling valve (12) | Slowly open the valves at the pressure gauge of the air conditioning extraction and recycling unit. Note the display information on the air conditioning extraction and recycling unit. Extract the refrigerant until there is no noticeable increase in weight of the extracted refrigerant. | |
5 | Detach pressure and suction line of air conditioning extraction and recycling unit | |
Workshop equipment
WE58.40-Z-1002-22A | Air conditioning service station |
Henviste dokumenter
- ah8330n000301a Oplysninger om håndtering af kølemidlet R134a
- ar8330t5470bac
- as8300z000101a Fare for eksplosion ved svejse- og loddearbejde på det lukkede klimaanlæg. Fare for forgiftning ved indånding af overophedet kølemiddeldamp. Fare for personskade ved hud- og øjenkontakt med flydende kølemiddel
- wf5850t833001a