ar8330t1780baf

Discharge air conditioning system

Type ar · emne 83.30 · version 0100 · 2006-07-26

Gælder for: MODELS NMB613.358 /388 with CODE (HKF) Webasto Top 2002 Aerosphere air conditioning with roof heater MODELS NMB613.358 /388 with CODE (HKF) Webasto Top 2002 Aerosphere air conditioning with roof heater with CODE (HO4) Front air conditioning

Ikke tilgængelig på “da”; vises på Engelsk.

Placering

Funktionsgruppe 3 Karrosseri › 83 Klimatisering › 83.30 Klimaanlæg — Serie 613 (modeller 358, 388)

EinPAS 39 Varmesystem/ventilation/køling › 39.15 Klimatisering › 39.15.5 Klimaanlæg komplet — Serie 613 (modeller 358, 388)

AR83.30-T-1780BAF

Discharge air conditioning system

8.2.05

MODELS NMB613.358 /388 with CODE (HKF) Webasto Top 2002 Aerosphere air conditioning with roof heater

MODELS NMB613.358 /388
with CODE (HKF) Webasto Top 2002 Aerosphere air conditioning with roof heater
with CODE (HO4) Front air conditioning

Discharge air conditioning system

T83.55-0025-01

3 Shutoff valve on thrust side

4 Shutoff valve on intake side

11 Pressure-side testing and filling valve

12 Suction-side testing and filling valve

Danger!

Risk of explosion from welding or soldering work on closed air conditioning system. Risk of poisoning from inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant.

Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been discharged.

AS83.00-Z-0001-01A

Notes on handling refrigerant R134a

Air conditioning with refrigerant R134a

AH83.30-N-0003-01A

1

Energize electromagnetic shutoff valve

AR83.30-T-5470BAC

Cable for activation of solenoid

WF58.50-T-8330-01A

2

Detach protective caps from the pressure-side testing and filling valve (11) and from the suction-side testing and filling valve (12)

3

Connect pressure and suction line of the air conditioning extraction and recycling unit to the pressure-side testing and filling valve (11) and to the suction-side testing and filling valve (12)

Refer to the operating instructions for the air conditioning extraction and recycling unit.

Ensure that the pressure-side shutoff valve (3) and the suction-side shutoff valve (4) are unscrewed completely.

*WE58.40-Z-1002-22A

4

Extract refrigerant using the pressure-side testing and filling valve (11) and the suction-side testing and filling valve (12)

Slowly open the valves at the pressure gauge of the air conditioning extraction and recycling unit.

Note the display information on the air conditioning extraction and recycling unit.

Extract the refrigerant until there is no noticeable increase in weight of the extracted refrigerant.

5

Detach pressure and suction line of air conditioning extraction and recycling unit

*WE58.40-Z-1002-22A

Workshop equipment

WE58.40-Z-1002-22A

Air conditioning service station