AR83.30-T-1777AB | Fill air conditioning system (liquid) | 17.6.03 |
MODELS NMB671.030 with CODE (HKC) Sütrak AC 353 air conditioning without roof heater
T83.30-0081-11
1 Pressure-side testing and filling valve
3 Suction-side testing and filling valve
Modification notes
Charging | |||
Danger! | Risk of explosion from welding or soldering work on closed air conditioning system. Risk of poisoning from inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant. | Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been discharged. | |
| Notes on handling refrigerant R134a | Air conditioning with refrigerant R134a | |
1 | Open electromagnetic shutoff valve | Manual opening | |
Electrical opening | |||
2 | Evacuate air conditioning system and carry out leak check | ||
3 | Charge air conditioning system with refrigerant | Observe the following: Observe the operator's manual of the air conditioning vacuum and recycling unit. Fill in the prescribed total filling quantity via the pressure-side testing and filling valve (1) only. | |
| |||
| |||
4 | Switch off air conditioning vacuum and recycling unit | | |
5 | Fully unscrew shutoff valve from suction-side testing and filling valve (3) | Screw on cap above shutoff valve. | |
6 | Remove pressure and suction line of air conditioning vacuum and recycling unit from the pressure-side testing and filling valve (1) and from the suction-side testing and filling valve (3) | ||
7 | Screw on caps above the pressure-side testing and filling valve (1) and the suction-side testing and filling valve (3) | ||
8 | Close electromagnetic shutoff valve | Only when the electromagnetic shutoff valve was opened with the aid of a magnet. | |
9 | Remove electrical line that is used to activate the electromagnetic shutoff valve | Only when the electromagnetic shutoff valve was opened via activation. |
Air conditioning
Number | Designation | Model | ||
BF83.30-N-1001-01E | Total refrigerant filling capacity | KG | 7.0 | |
Specifications for Operating Fluids | Sheet | |||
Workshop equipment
WE58.40-Z-1002-22A | Air conditioning service station |
Henviste dokumenter
- ah8330n000301a Oplysninger om håndtering af kølemidlet R134a
- ar8330t1762ab
- ar8330t5460aa
- ar8330t5470bac
- as8300z000101a Fare for eksplosion ved svejse- og loddearbejde på det lukkede klimaanlæg. Fare for forgiftning ved indånding af overophedet kølemiddeldamp. Fare for personskade ved hud- og øjenkontakt med flydende kølemiddel