AR83.50-D-6940HK | Remove/install refrigerant lines to evaporator unit of rear air conditioning | 8.12.05 |
MODEL 903.672 with CODE (HK2) Air conditioning in rear with underfloor condenser
D83.50-1236-09
1 Bitumen insulating tape
2 Line connection
3 Line bracket
M Refrigerant line on pressure side
N Refrigerant line intake side
4 Union nut
7 Refrigerant line on pressure side
9 Expansion valve
| Remove/install | ||
Danger! | Risk of explosion from welding or soldering work on closed air conditioning system. Risk of poisoning from inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant. | Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been discharged. | |
| Conduct if air conditioning system is damaged or leaking | All models | |
| Protect air conditioning circuit and components from moisture when carrying out repair work | All models fitted with air conditioning | |
| Notes on handling refrigerant R134a | Air conditioning with refrigerant R134a | |
1 | Discharge air conditioning system | ||
2 | Remove evaporator unit paneling | ||
3 | Remove bituminous insulating tape (1) | Installation: Carefully attach new bituminous insulating tape (1). | |
4 | Detach line connectors (2) | Plug openings Installation: Use new sealing rings. Coat sealing rings with compressor oil before installation. | |
| |||
| |||
| |||
| Compressor oils | ||
5 | Unscrew union nuts (4). | Plug openings Installation: Use new sealing rings. Coat sealing rings with compressor oil before installation. | |
| |||
| |||
| Compressor oils | ||
6 | Remove suction-side refrigerant line (N) and thrust-side refrigerant line (7) on expansion valve (9) | Plug openings Installation: Use new sealing rings. Coat sealing rings with compressor oil before installation. | |
| |||
| |||
| Compressor oils | ||
7 | Detach line holder (3) | ||
8 | Remove thrust-side refrigerant line (M) and suction-side refrigerant line (N) | ||
9 | Install in the reverse order | Only install evaporator unit paneling after the air conditioning has been filled and checked. | |
10 | Replace fluid reservoir | The filter drier is integrated into the fluid reservoir. | |
11 | Evacuate the air conditioning system, refill it, and then check the system to make sure that it functions correctly and does not leak. | ||
| |||
|
Rear air conditioning unit
Number | Designation | Model | |
BA83.50-N-1001-01C | Refrigerant line to solenoid valve | Nm | 16 |
BA83.50-N-1002-01C | Bolt, refrigerant lines to evaporator unit expansion valve | Nm | 10 |
BA83.50-N-1005-01C | Line connection, thrust side refrigerant lines | Nm | 16 |
BA83.50-N-1006-01C | Line connection, intake side refrigerant lines | Nm | 30 |
Air conditioning
Number | Designation | Model | ||
BF83.30-N-1009-01A | Total filling capacity, refrigerant | kg | 1,85 | |
Specifications for Operating Fluids | Sheet | |||
BF83.30-N-1011-01A | Total filling capacity for compressor oil of air conditioning system | cm3 | 250 | |
Specifications for Operating Fluids | Sheet | |||
Set of plugs
129 589 00 91 00
Repair materials
Number | Designation | Order number |
BR00.45-Z-1062-01A | Insulation | A 901 831 13 96 |
Odkazované dokumenty
- ah8330n000301a Pokyny k manipulaci s chladivem R134a
- ah8330n000401a Postup při poškozené, resp. netěsné klimatizaci
- ah8330n000501a Ochrana okruhu a součástí klimatizace při opravárenských pracích před vlhkostí
- ar8330d1760a
- ar8330d6520na
- ar8350d5010na
- as8300z000101a Nebezpečí exploze při svářečských nebo pájecích pracích na uzavřené klimatizaci. Nebezpečí otravy při vdechnutí přehřátých výparů chladiva. Nebezpečí poranění při kontaktu očí a kůže s tekutým chladivem
- bb0040p036200a Kompresorové oleje (specifikace 362.0)