Shown on model 613.455 with air conditioning system Konvekta ACX 641 SAPTCO without roof heater, code HKB |
2 | Shutoff valve, pressure side |
3 | Test and filling valve, pressure side |
4 | Test and filling valve, intake side |
5 | Shutoff valve, intake side |
T83.30-0073-06
Draining | |||
Danger | Risk of explosion caused by welding or soldering work on closed air conditioning system. Risk of poisoning caused by inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant. | Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been drained. | |
Topical note | Protect air conditioning circuit and components from moisture when carrying out repair work | ||
Notes on handling refrigerant R134a | |||
1 | Open electromagnetic shutoff valve |
| |
Electric opening | |||
2 | Connect pressure and suction line of air conditioning vacuum and recycling unit to test and filling valve, pressure side (3) and test and filling valve, intake side (4) | Observe operating instructions for air conditioning system vacuum and recycling unit. | |
3 | Remove cover cap at shutoff valve, pressure side (2) and at shutoff valve, intake side (5) | ||
4 | Screw in shutoff valve, pressure side (2) and shutoff valve, intake side (5) approx. 3 turns | By screwing in the shutoff valve, pressure side (2) and the shutoff valve, intake side (5), the test and filling valve, pressure side (3) and the test and filling valve, intake side (4) are opened. | |
5 | Extract refrigerant via test and filling valve, pressure side (3) and test and filling valve, intake side (4) | Open valves at manometer of air conditioning vacuum and recycling unit slowly. | |
6 | After emptying the air conditioning system, unscrew shutoff valve, pressure side (2) and shutoff valve, intake side (5) up to end stop | By unscrewing to the end stop, the test and filling valve, pressure side (3) and the test and filling valve, intake side (4) are closed. | |
7 | Switch off air conditioning vacuum and recycling unit | Observe operating instructions for air conditioning system vacuum and recycling unit. | |
8 | Remove pressure and suction line of air conditioning vacuum and recycling unit | Observe operating instructions for air conditioning system vacuum and recycling unit. | |
9 | Screw cover cap at shutoff valve, pressure side (2) and at shutoff valve, intake side (5) on tight |
Odkazované dokumenty
- ah8330n000301a Pokyny k manipulaci s chladivem R134a
- ah8330n000501a Ochrana okruhu a součástí klimatizace při opravárenských pracích před vlhkostí
- ar8330t5460aa
- ar8330t5470bac
- as8300z000101a Nebezpečí exploze při svářečských nebo pájecích pracích na uzavřené klimatizaci. Nebezpečí otravy při vdechnutí přehřátých výparů chladiva. Nebezpečí poranění při kontaktu očí a kůže s tekutým chladivem