Evacuating air conditioning system, leak test

16.6.03

MODELS NMB671.030 with CODE (HKC) Sütrak AC 353 air conditioning without roof heater

Evacuating air conditioning system, leak test

T83.30-0081-11

1 Pressure-side testing and filling valve

2 Pressure gage

3 Suction-side testing and filling valve

Modification notes

9.12.04

Open electromagnetic shutoff valve, added

Step 1

Evacuating

Danger!

Risk of explosion from welding or soldering work on closed air conditioning system. Risk of poisoning from inhaling overheated refrigerant vapors. Risk of injury to skin and eyes caused by contact with liquid refrigerant.

Never perform welding work on or near a closed air conditioning system. No smoking or open flames. Wear safety glasses and protective gloves. Work only in well ventilated areas. Carry out repair work on the air conditioning system circuit only after the system has been discharged.

AS83.00-Z-0001-01A

Notes on handling refrigerant R134a

Air conditioning with refrigerant R134a

AH83.30-N-0003-01A

1

Open electromagnetic shutoff valve

Manual opening

AR83.30-T-5460AA

Electrical opening

AR83.30-T-5470BAC

2

Screw off caps above the pressure-side testing and filling valve (1) and the suction-side testing and filling valve (3)

3

Connect pressure and suction line of air conditioning vacuum and recycling unit to the pressure-side testing and filling valve (1) and to the suction-side testing and filling valve (3)

Observe the operator's manual of the air conditioning vacuum and recycling unit.

*WE58.40-Z-1002-22A

4

Screw shutoff valve into suction-side testing and filling valve (3) 2 to 5 turns

Remove cap above shutoff valve.

5

Evacuate air conditioning system

Evacuate air conditioning system circuit until maximum possible vacuum has been reached, but for no less than 8 hours.

Leak test

6

Switch off air conditioning vacuum and recycling unit

Close valves of air conditioning vacuum and recycling unit. Closing the valves prevents an incorrect leak test of the air conditioning vacuum and recycling unit.

7

Read off vacuum indication on pressure gauge (2) of air conditioning vacuum and recycling unit

Note vacuum pressure value

8

Read off vacuum indication on pressure gauge (2) again after a waiting time of 10 minutes

Compare current vacuum value to the recorded vacuum value.

If a drop in vacuum is detectable:

Fill air conditioning without performing leak test

After filling the air conditioning system, check for leaky areas:

AR83.30-T-1777AB

Inspect the refrigeration circuit for leaks.

Before repairing leaky area empty air conditioning system:

AR83.30-T-1209-01C

Discharge air conditioning system

Check for leaky areas again after the repair work:

AR83.30-T-1780AB

Repeat steps 1 to 8.

9

Fill air conditioning system

Do not evacuate nor perform leak test.

AR83.30-T-1777AB

Workshop equipment

WE58.40-Z-1002-22A

Air conditioning service station